TM1700-series
Circuit Breaker Analyzer System
3
1 2 3 4 5 6 71 2
15 16 17 19 15 20 21 22 23
10
11
12
18
9
14
13
8
Features and benefits
1. Input for external clamp-on CT
2. Control section
▪ Three independent contact functions
▪ Pre-programmed sequences C, O, C–O, O–C, O–C–O
▪ Timing of a and b auxiliary contacts
▪ Coil current, voltage and resistance
3. Timing Aux section
▪ Six galvanic isolated channels
▪ Polarity insensitive
▪ Dry and wet auxiliary contacts
4. Timing M/R section
▪ Six inputs
▪ High resolution 15μV and up to 40 kHz sampling
▪ Main and parallel resistor contact timing
▪ Resistance value of parallel resistors
5. Analog section
▪ Six channels (three optional)
▪ Supports industrial analog transducers
▪ Insulated channels, measure up to 250 V whithout volt. div.
▪ High resolution 0.3 mV, sampling rate 40 kHz
6. Digital section
▪ Six channels
▪ Incremental transducers with RS422
▪ Up to ±32000 pulses resolution
▪ Up to 40 kHz sampling
7. Mains input
8. DC out
▪ General voltage source ,12 V
9. DRM
10. Earth (ground) terminal
11. Ethernet port
12. USB ports
13. Trig IN
▪ Used for external trig of the unit. Contact make / break or
voltage signal.
14. DCM interface
15. Navigation buttons
▪ Works in parallell with the touch screen buttons.
▪ Most of the CABA Local functions are controlled by the ten
navigation buttons.
16. Touch screen On/Off
17. On-screen keyboard On/Off
18. Display (touch screen)
▪ High brightness for good visibility in direct sunlight.
19. Brightness setting
20. POSITION
▪ Indicates the position of the circuit breaker main contacts if
the coil circuit is connected to the control section.
21. SEQUENCE
▪ Indicates the next operation of the circuit breaker. If Auto-de-
tect breaker state is enabled in CABA Local or CABA Win, only
possible sequences for the circuit breaker are selectable.
22. OPERATE/MEASURE
▪ Initiates the selected operation sequence and makes the mea-
surement. Green “READY” LED must be lit before turning the
rotary switch. The yellow “OPERATING” LED is lit as long as
the sequence is performed.
23. On/Off switch
Comentários a estes Manuais